Turn the dial (2) on the nozzle needle (25) to the
desired position.
Place the stuffing box gland (8) on the nozzle
needle (25).
Hand-tighten the stuffing box screws (28).
Unscrew the nozzle needle by a half turn.
The torque for the stuffing box screws varies
depending on the equipment:
For models with DN 15 to DN 32, the required
torque is 7 Nm.
For models with DN 40 and DN 50, the required
torque is 11 Nm.
Tighten the stuffing box screws to the specified
torque.
Turn the nozzle needle to closed position with a
torque of 7 Nm.
Place the control lever (1) on the nozzle needle.
Align the scale (9) on the dial (2) so that the "0"
mark is in the centre of the dial.
Screw the hex nut (30) onto the nozzle needle,
holding the control lever firmly.
Tighten the hex nut to a torque of 20 Nm.
Insert the sealing ring (7).
Screw in the sealing plug (6) or sampling valve
to a torque of 130 Nm.
Fit the actuator as described on page 34.