= Factory setting
WC control with KB emergency opening WC control with adjustable unlocking time
Push button
inside
Push button
outside
4
Push button
outside
Push button
inside
4
à Set “PE1” or “PE2” to WC control.
à Set “PA1” or “PA2” to exit only function.
Set “PA1” or “PA2” to alarm WC control function.
à Set “Hold-open times, 1-leaf opening” to the desired time (0-60s).
à GC 307+ inside and outside*: Door control to 1 (Auto)
à GC 307+ inside*: Output mode to 1 (Toggle NO)
à GC 307+ outside*: Door control to 4 (Restroom)
Note:
The door can be unlocked at any time via KB.
After 30 minutes, an external warning signal
(acoustic or optical) is triggered.
Note:
The door also unlocks automatically after the
set “Aut. reset” time has elapsed.
*Only possible via the remote control (100061)
Acoustic signal
1
0
2
3
4
5
6
7
shor
t sound
long sound