CommissioningGC 363 R / SF
X
Testing the emission area.
à The Air: Width parameter must be set identically (see chapter 7).
à The complete width of the door must be covered.
à Test the width of the required area using a piece of paper (DIN A4), since
the spot nder detects over the whole emission area.
Standard-conform sensor setting according to DIN 18650 / EN 16005
Installation height Detection width DIN 18650 / EN 16005
2.00 m
2.20 m
2.50 m
3.00 m
3.50 m
2.00 m
2.20 m
2.50 m
2.50 m / 3.00 m
2.50 m / 3.00 m