Maintenance GC 363 R / SF
28
10 Maintenance
X
The visual parts must be cleaned at least once a year.
X
Do not use aggressive cleaning agents or chemicals.
11 Error messages and troubleshooting
LCD
display
Eect Cause Elimination
E1 The ORANGE
LED ashes 1 x
The sensor has de-
tected an internal
error.
X
Replace the sensor.
E2 The ORANGE
LED ashes 2 x
The power supply
is too low or too
high.
X
Check the power supply (in
the LCD diagnosis menu).
X
Check the wiring.
E4 The ORANGE
LED ashes 4 x
The sensor is
receiving too little
AIR energy.
X
Reduce the AIR angle.
X
Increase the AIR immunity
lter (values > 2.8 m).
X
Disable 1 curtain.
E5 The ORANGE
LED ashes 5 x
The sensor is
receiving too much
AIR energy.
External elements
are interfering with
the sensor.
X
Slightly increase the AIR
angle.
X
Check for interfering ele-
ments and eliminate if neces-
sary (e.g. lamps or earthing of
the drive housing).
X
Reduce the AIR immunity
lter to 1, 2 or 3.
E6 GC 363 SF only:
The ORANGE
LED ashes 6 x
The radar output is
defective.
X
Replace the sensor.
E7 GC 363 SF only:
The ORANGE
LED ashes 7 x
Interference of the
internal radar test.
X
Change the radar angle.
X
Change the radar antenna.
X
Replace the sensor if the
ORANGE LED continues to
ash.
E8 The ORANGE
LED ashes 8 x
The AIR energy
transmitter is
defective.
X
Replace the sensor.
E9 The ORANGE
LED ashes 9 x
The internal radar
reference is incor-
rect.
X
Replace the sensor.

Other manuals for GEZE GC 363 SF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GEZE GC 363 SF and is the answer not in the manual?

GEZE GC 363 SF Specifications

General IconGeneral
BrandGEZE
ModelGC 363 SF
CategorySecurity Sensors
LanguageEnglish

Related product manuals