0020167175_01 - 02/13 - Glow-worm
Compare the value measured with the values indicated in the
table below.
Gas adjustment G20 G31
CO
2
case ON 9 ± 0.2 % 10.1 ± 0.2 %
CO
2
case OFF 9.2 ± 0.3 % 10.3 ± 0.3 %
i
IMPORTANT:
Safe combustion can only be veri ed by measuring CO/
CO
2
ratio. This must not exceed the value shown in the
table under the section "Maximum Rate and Adjustment".
15.1.3 Restarting
Replace the cap
Replace the appliance front panel.
Note: following the replacement of the front panel, the CO
2
value
will change: you can check that the value "case on" is correct by
the values in the previous table.
1
2
Key
1 Serial number stickers
2 Data label location
Firmly attach the gas replacement label to the appliance in the
corresponding location (1) on the electrical box.
15.2 Restart - re-check commissioning
Before putting the appliance into operation, follow the
instructions within the chapter Speci c adjustment.
16 Draining
16.1 Heating circuit
B
A
1
2
2
Key
1 Length of hose (not supplied)
2 Drain valve
Drain down the heating circuit of the boiler only, by closing
the heating ow and return isolating valves. See chapter
"Hydraulic connection > Gas and water connections"
Open the drain point (2). Attach a length of hose (1) if
required.
After draining, close the drain valve (2) and remove the hose.
16.2 Domestic Hot water circuit
Drain the Domestic Hot Water circuit by closing the cold-water
isolation valve.
Open one or more hot water taps to drain the hot water circuit.
17 Servicing
To ensure the continued e cient and safe operation of the
boiler it is recommended that it is checked and serviced as
necessary at regular intervals.
The frequency of servicing will depend upon the particular
installation conditions and usage. However it is recommended
that the boiler is inspected as part of a service at least once a
year.
If this appliance is installed in a rented property there is a duty of
care imposed on the owner of the property by the current issue of
the Gas Safety (Installation and Use) Regulations, Section 35.
Servicing/maintenance should be carried out by a competent
person approved at the time by the Health and Safety
Executive in accordance with the rules in force in the countries
of destination.
MAINTENANCE
- 33 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Glow-worm ULTIMATE 30c and is the answer not in the manual?

Glow-worm ULTIMATE 30c Specifications

General IconGeneral
Boiler TypeCombi
Fuel TypeNatural Gas
Central Heating Output30 kW
ErP Efficiency RatingA
MountingWall-mounted
CH Output30 kW
DHW Output30 kW
Standard Warranty5 Years
Dimensions740x418x300mm

Related product manuals