Go Power! GP-SW3000, GP-SW2000, GP-SW1000and GP-SW600
Owner’s Manual
27
10. Configuring your GP-SW3000, GP-SW2000, GP-SW1000,
and GP-SW600
10.1 Configuring the Dip Switches
GP-SW3000, GP-SW2000, and GP-SW1000
For a typical North American system, set the Frequency to 60 Hz.
For more information on power saving, please see 5.10 and 5.11 sections
Switches are located on the front panel. Power saving is enabled and adjusted through dip
switches S1, S2, and S3 on the front of the inverter. To disable power saving, leave dip
switches S1, S2 and S3 in the OFF or 0 position
Power Saving S1 S2 S3
Disable OFF OFF OFF
> 7 W ON OFF OFF
> 15 W OFF ON OFF
> 20 W ON ON OFF
> 28 W OFF OFF ON
> 35 W ON OFF ON
> 42 W OFF ON ON
> 50 W ON ON ON
GP-SW1000, GP-SW2000, and GP-SW3000 GP-SW600
S4 Freq. (Hz) Dip Switch Freq. (Hz)
0 50 Up 50
1 60 Down 60
10.2 Other Dip Switches (Professional Installer Only)
The default voltage setting for the GP-SW600, GP-SW1000, GP-SW2000, and
GP-SW3000 is 115 V AC, however all these inverters may be configured for other
voltages by a professional installer via the two red dip switches located close to the AC
connection inside each unit. The unit must be restarted in order for any changes to take
effect.
SW1 SW2 VAC
Off Off 100
On Off 110
Off On 115
On On 120