BLOWER PERFORMANCE DATA
9
ACNF
0.1" 0.2" 0.3" 0.4" 0.5"
High 610 525 480 400 320
Low 545 470 400 340 250
High 610 525 480 400 320
Low 545 470 400 340 250
High 610 525 480 400 320
Low 545 470 400 340 250
High 610 525 480 400 320
Low 545 470 400 340 250
High 945 860 800 725 670
Low 850 800 725 680 600
High 945 860 800 725 670
Low 850 800 725 680 600
High 945 860 800 725 670
Low 850 800 725 680 600
High 945 860 800 725 670
Low 850 800 725 680 600
High 945 860 800 725 670
Low 850 800 725 680 600
High 1,060 985 895 805 720
Low 905 845 780 710 625
High 1,060 985 895 805 720
Low 905 845 780 710 625
High 1,060 985 895 805 720
Low 905 845 780 710 625
High 1,060 985 895 805 720
Low 905 845 780 710 625
High 1,060 985 895 805 720
Low 905 845 780 710 625
ACNF300816
ACNF31016
ACNF300016
ACNF300516
ACNF300616
ACNF240616
ACNF240816
ACNF241016
ACNF180516
ACNF180616
ACNF240016
ACNF240516
ACNF180616
CFM deliverd against External Static Pressure
Model Speed
ACNF180016
ACNF*****DA (with aluminum coils)
Heating Capacity/kW Correction Factor
Supply Voltage 240 230 220 210 208
Correction Factor 1.08 1.00 0.92 0.84 0.82