RS6200007r14
December 2017
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury due to improper
service procedures or services performed by an unqualified person.
Copyright © 2015-2017 Goodman Manufacturing Company, L.P.
ComfortNet
ASXC, DSXC, and GSXC Condensing Units,
ASZC, DSZC and GSZC
Split System Heat Pumps
with R-410A Refrigerant
Blowers, Coils, & Accessories
Service Instructions
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Goodman ComfortNet DSXC160481BC and is the answer not in the manual?

Goodman ComfortNet DSXC160481BC Specifications

General IconGeneral
BrandGoodman
Model NumberDSXC160481BC
CategoryHeat Pump
Cooling Capacity4 ton
SEER Rating16
RefrigerantR-410A
Compressor TypeScroll
Cooling Capacity (BTU/h)48000
Heating Capacity (BTU/h)48000
Voltage208/230V
Phase1
Sound Rating (dBA)72
HSPF Rating9.5

Summary

Service Instructions ComfortNet™

Important Information and Safety

Safe Refrigerant Handling

Product Identification

System Operation

System Operation (Continued)

Troubleshooting Chart

Cooling/HP Analysis Chart

Provides a chart for diagnosing cooling and heat pump issues.

Servicing

S-1 Checking Voltage

Procedure for checking system voltage.

Servicing (Continued)

Network Troubleshooting

Steps to troubleshoot ComfortNet™ system network issues.

PCBJA101-PCBJA102 Air Handler Diagnostic Codes

Lists diagnostic codes for specific air handler control boards.

ECM Motor Checks

General checks and troubleshooting for ECM motors.

Unitary Diagnostic Codes

Table detailing unitary diagnostic codes and their meanings.

Electrical Checks - Low Voltage Control Circuits

Procedures for checking low voltage control circuits.

S-17 Checking Compressor

Procedures for checking the compressor.

Motor Control Circuits

Troubleshooting guide for motor control circuits.

S-101 Leak Testing (Nitrogen or Nitro-Traced)

Method for leak testing the system with nitrogen.

S-10A Copeland Comfort Alert™ Diagnostics

Diagnostics for UC control with Comfort Alert™.

S-16G Checking Emerson Ultratech™ ECM Motors

Guide for diagnosing Emerson Ultratech™ ECM motors.

Electrical Checks - High Voltage Power Circuits

Procedures for checking high voltage power circuits.

S-16H ECM CFM Adjustments AVPTC/MBVC

Guide for adjusting ECM motor CFM settings.

S-17A Resistance Test

Procedure for testing compressor winding resistance.

S-21 Checking Reversing Valve and Solenoid

Procedure to check the reversing valve.

Data Line Voltage Troubleshooting and Bias Switches

Troubleshooting communication data lines and bias switches.

S-102 Evacuation

Procedure for system evacuation.

S-17B Ground Test

Procedure for checking compressor ground faults.