BLOWER PERFORMANCE SPECIFICATIONS
8
*MVC960403BNA
Cooling Speed
(@ .1" - .8" w.c. ESP)
*MVC960403BNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
Ta p A dju st
High-Stage
CFM
Low-Stage
CFM
Ta p A dju st
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10% 536 363
A
Minus 10% 445 380 n/a
Minus 5% 566 383 Minus 5% 469 401 n/a
Normal 596 403 Normal 494 422 n/a
Plus 5% 626 423 Plus 5% 519 443 n/a
Plus 10% 656 443 Plus 10% 543 464 65
B
Minus 10% 716 474
B
Minus 10% 498 424 n/a
Minus 5% 756 501 Minus 5% 525 447 n/a
Normal 796 527 Normal 553 471 64
Plus 5% 836 553 Plus 5% 581 495 61
Plus 10% 876 580 Plus 10% 608 518 58
C
Minus 10% 877 608
C
Minus 10% 541 469 n/a
Minus 5% 925 641 Minus 5% 571 495 62
Normal 974 675 Normal 601 521 59
Plus 5% 1,023 709 Plus 5% 631 547 56
Plus 10% 1,071 743 Plus 10% 661 573 54
D
Minus 10% 1,073 723
D
Minus 10% 608 517 58
Minus 5% 1,132 763 Minus 5% 642 545 55
Normal 1,192 803 Normal 676 574 53
Plus 5% 1,252 843 Plus 5% 710 603 50
Plus 10% 1,311 883 Plus 10% 744 631 48
*MVC960603BNA
Cooling Speed
(@ .1" - .8" w.c. ESP)
*MVC960603BNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 20 - 50°F)
Ta p A dju st
High-Stage
CFM
Low-Stage
CFM
Ta p A dju st
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10% 539 358
A
Minus 10% 858 600 n/a
Minus 5% 569 378 Minus 5% 905 634 n/a
Normal 599 398 Normal 953 667 n/a
Plus 5% 629 418 Plus 5% 1,001 700 n/a
Plus 10% 659 438 Plus 10% 1,048 734 n/a
B
Minus 10% 735 501
B
Minus 10% 953 666 n/a
Minus 5% 776 529 Minus 5% 1,006 703 n/a
Normal 817 557 Normal 1,059 740 50
Plus 5% 858 585 Plus 5% 1,112 777 48
Plus 10% 899 613 Plus 10% 1,165 814 46
C
Minus 10% 906 626
C
Minus 10% 1,042 727 n/a
Minus 5% 957 661 Minus 5% 1,100 768 48
Normal 1,007 696 Normal 1,158 808 46
Plus 5% 1,057 731 Plus 5% 1,216 848 44
Plus 10% 1,108 766 Plus 10% 1,274 889 42
D
Minus 10% 1,091 729
D
Minus 10% 1,134 793 47
Minus 5% 1,151 770 Minus 5% 1,197 837 45
Normal 1,212 810 Normal 1,260 881 42
Plus 5% 1,273 851 Plus 5% 1,323 925 40
Plus 10% 1,333 891 Plus 10% 1,386 969 38
Notes
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
Formost jobs, about 400 CFM perton when cooling is desirable.

Related product manuals