18
minimum clearances between the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake
terminations of a single unit.
If more than one direct vent furnace is to be installed horizontally through a common side wall, maintain the clearances as in the
following figure. Always terminate all exhaust vent outlets at the same elevation and always terminate all air intakes at the same
elevation.
CONCENTRIC VENT TERMINATION
Refer to the directions provided with the Concentric Vent Kit
(DCVK) for installation specifications.
SIDE WALL VENT KIT
This kit is to be used with 2” or 3” direct vent systems. The vent kit must terminate outside the structure and may be installed with
the intake and exhaust pipes located side-by-side or with one pipe above the other. These kits are NOT intended for use with single
pipe (non-direct vent) installations.
Refer to the directions furnished with the Side Wall Vent Kit (p/n 0170K00000S or 0170K00001S) for installation specifica-
tions.
C
ONDENSATE
D
RAIN
L
INES
& D
RAIN
T
RAP
A condensing gas furnace achieves its high level of efficiency by extracting heat from the products of combustion to the point where
condensation takes place. The condensate must be collected in the furnace drain trap and routed to an appropriate drain
location in compliance with local and national codes.
Follow the bullets listed below when installing the drain system. Refer to the following sections for specific details concerning furnace
drain trap installation and drain hose hook ups.
Vertical Installation
Horizontal Installation
Side Wall Vent Kit
Figure 19
Combustion Air Intake may also be snorkeled
to obtain 12” min ground clearance.
Alternate Vent Termination Above Anticipated Snow Level
(Dual Pipe)
Figure 17
90°
ELBOWS
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
3”-24” BETWEEN PIPES
Termination of Multiple Direct Vent Furnaces
Figure 18
3” MIN
12” MIN TO GRADE OR HIGHEST
ANTICIPATED SNOW LEVEL
3”MIN
24”MAX
12” MIN SEPARATION