TROUBLESHOOTING
Symptom Probable Cause Corrective Action
A Meter counter does
not operate (Normal
fuel ow)
Broken counter
assembly
Replace counter
Counter alignment Look for loose or
missing fasteners, bent
or misaligned parts
Foreign material in
counter assembly
Remove and clean
counter assembly
Missing or worn bevel
gear
Replace bevel gear
B Meter counter does
not operate
(Little or no fuel ow)
Clogged strainer in
meter inlet
Clean or replace
strainer
Jammed rotors from
foreign material in rotor
assembly
Remove and clean rotor
assembly
Other system
components
malfunctioning
Check all system
components tank to
nozzle for clogs and/or
malfunctions Repair as
necessary
C Fuel leakage Leakage between
coverplate and housing
Remove coverplate and
inspect for damaged,
missing or incorrectly
seated seal Replace
as required
Leakage at ttings Remove ttings and
inspect for damaged,
missing or incorrectly
seated seals Replace
as required
Leakage at threads Remove meter and
reseal all threaded
connections with thread
tape or pipe thread
sealing compound
approved for use with
ammable liquids�