EasyManuals Logo

Grasslin DTMV40 Series User Manual

Grasslin DTMV40 Series
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
• Disconnectpoweratthecircuitbreaker(s)ordisconnectswitch(es)beforebeginning
installationorservicing.
• Morethanonecircuitbreakerordisconnectswitchmayberequiredtode-energizethe
equipmentbeforeservicing.
• Donotusethemanualoffpositionofthetimerforequipmentservicing.Alwaysdiscon-
nectthepoweratthecircuitbreaker(s)ordisconnectswitch(es).
• UseCOPPERconductorsONLY.
• For40amploads,use#8AWGwire,rated90˚Cmin.
• Wireinaccordancewithnationalandlocalelectricalcoderequirements.
DTMV40 Series
TimeInitiated,Temperature,
PressureorTimeTerminatedMulti-Voltage
40ADefrostTimers
WARNING
Risk of Fire or Electric Shock
• Rotatetimerdialclockwiseonly.
CAUTION
Risk of Damage to Timer
1
Paragon Precision
TIME INITIATED, TIME TERMINATED
Grasslin
Mode Selection Wiring Diag.
TIME INITIATED, PRESSURE TERMINATED
(Separate Pressure Switch Required (see instructions)
TIME INITIATED, REMOTE TEMPERATURE OR
PRESSURE TERMINATED
STARTUP PROCEDURE
1. Determine model to be replaced (Grasslin or Competitors)
from table below.
2. Set Mode Selection (S1 BLUE DIP Switch
Fig. A) See table below and instructions
on page 5.
3. Apply corresponding Terminal
Identification and Door labels –see retrofit
kit instructions.
4. Set correct input voltage (S2 RED DIP
Switch – Fig. B).
5. Follow installation and programming instructions.
The DTMV40 can be configured for
either 120 or 208/240VAC. Locate RED
DIP Switch to the right of timer module.
For:
120VAC slide DIP switch UP
208/240VAC slide DIP switch DOWN
TImer Mechanism
Step 2
Interior
Protective
Cover
Step 1
Ground Lug
2-1/2”
6-1/8”
INSTALLATION
Note: For outdoor locations, raintight, or wet location conduit
hubs that comply with requirements of UL 514B (standard for
fittings for conduit and outlet boxes) are to be used.
1. Open door and then remove interior protective cover by
releasing spring clip on bottom.
2. Remove timer mechanism by releasing spring clip on bot-
tom.
3. Select knockouts to be used. Remove inner 1/2” knockout
by inserting a screwdriver in the slot and carefully punch
knockout loose. Remove slug. If 3/4” knockout is required,
remove the outer ring with pliers after removing the 1/2”
knockout. Smooth edges with knife if necessary.
4. Place enclosure in desired mounting location and mark the
three mounting holes (refer to diagram below). Start by
placing set screw on top and attaching enclosure over
keyhole: then screw in remaining two screws on bottom.
5. Connect conduit hubs to conduit before connecting the
hubs to the enclosure. After inserting hubs into enclosure,
carefully tighten hub lock nut. Do not over-torque.
6. Verify voltage selection. 120VAC position switch UP;
208/240VAC – position switch DOWN (refer to Fig. B).
7. Wire in accordance with National and Local
Codes.
8. Gr
ounding: Terminate all ground wires to ground lug on
bottom of enclosure.
9. Replace interior pro-
tective cover.
UL TYPE 3R Enclosure
Bracket Mount
Input Voltage Switch (S2)
Mode Selection Switch (S1)
http://waterheatertimer.org/Intermatic-Defrost-timers-and-manuals.html

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grasslin DTMV40 Series and is the answer not in the manual?

Grasslin DTMV40 Series Specifications

General IconGeneral
Mounting TypeDIN Rail
Contact ConfigurationSPDT
Voltage230V AC
Number of Channels1
Timing Range1 min to 168 hours
DisplayLCD
Protection RatingIP20

Related product manuals