Multi Variable Air Conditioners Ducted Type Indoor Unit
4
No. Name Appearance Q'ty Usage
6
M10 Washer (Spring Washer
M10X2.6)
4
To be used together with the hanger bolt for
installing the unit.
7 Insulation 1 To insulate the gas pipe
8 Insulation 1 To insulate the liquid pipe
9 Sponge 2 To insulate the drain pipe
10 Fastener 8 To fasten the sponge
3.2 Location for Installation
(1)This appliance shall not be installed a corrosive environment [i.e. laundry, etc.]
(2)The framework the unit is attached to must be strong enough to support units' weight.
(3)The condensate drain pipe must be properly sized/sloped to ensure proper drainage.
(4)Remove all obstacles at inlet or outlet to ensure good air circulation.
(5)Observe all dimensions below to ensure there's enough room for maintenance.
(6)Keep the unit away from any heating source, inflammable gas or smoke.
(7)This is a concealed ceiling type unit.
(8) Indoor and outdoor unit supply power and control wiring should be kept at least
1m(39-3/8 in.) from any TV set or radio. Electrical appliances may create interference
(noise) even if wiring is in excess of 1m(39-3/8 in.). Strong electrical signals may still
create interference.
Unit: mm(in.)
Fig 3.2.1