DC Inverter Multi VRF System User Manual
9
Fig.6
Dimension of outdoor connection pipe
Basic module
Pipe dimension
Connection method
Gas pipe (mm)
Liquid pipemm
GMV-120WL/A-T
φ15.9
φ9.52
GMV-140WL/A-T
φ15.9
φ9.52
GMV-160WL/A-T
φ19.05
φ9.52
GMV-120WL/A-X
φ15.9
φ9.52
GMV-140WL/A-X
φ15.9
φ9.52
GMV-160WL/A-X
φ19.05
φ9.52
4.2.4 Selection of Indoor Branches
Select indoor branches according to the total capacity of downstream indoor units. If the
capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.