DC Inverter Multi VRF System User Manual
10
R410A Refrigerant system
Total capacity of downstream indoor units X (kW)
Model
Y type branch
X20
FQ01A
20X30
FQ01B
30X70
FQ02
70X135
FQ03
135X
FQ04
4.2.5 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor units; If
the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Fig.8
Total capacity of downstream indoor units C (kW)
Gas pipemm
Liquid pipemm
C ≤5.6
Φ12.7
Φ6.35
5.6C≤14.2
Φ15.9
Φ9.52
14.2C≤22.4
Φ19.05
Φ9.52