GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
233
Possible reason
Electronic expansion valve doesnt operate normally;
ODU pipeline is blocked;
Troubleshooting:
2.2.4.138 UC Setting of master IDU is done
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This code is status code, not an error. During commissioning, it indicates that setting of master IDU
is done.
Possible reason——
Troubleshooting:
——
2.2.4.139 UL Compressor emergency operation DIP switch error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If setting of compressor emergency operation DIP switch is not within the setting range, it will
indicate this error.
Possible reason——
Troubleshooting:
Reset the DIP switch according to relevant sheet.