GREE                                                                        GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 
    86   
unit).   
If  no  button  operations  are  performed  on  the  master  unit  for  five  minutes,  the  function  setting 
automatically quits and the unit restores the current status.   
The default factory setting is “00”, that is, no silent mode. 
② A6 Unit cooling/heating function settings 
Step 1: Confirm entering the A6 unit cooling/heating function settings. The master unit is displayed 
as follows: 
Step 2: Select a corresponding cooling/heating function by pressing "SW1 (UP)" or "SW2 (DOWN)". 
Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows: 
On the master unit, press "SW6" to return to the upper level (press "SW6" in setting status to return 
to the upper level; press "SW6" after settings are completed to restore the normal operating status of the 
unit).   
If  no  button  operations  are  performed  on  the  master  unit  for  five  minutes,  the  function  setting 
automatically quits and the unit restores the current status.   
The default factory setting is “nA” cooling/heating. 
③ A2 Indoor unit pipeline refrigerant recovery 
Step 1: Confirm entering the A2 refrigerant recovery operation settings. The master unit is displayed 
as follows: 
Refrigerant Recovery Code 
Step 2: The default setting is “01”. Select "01" or "02" by pressing "SW1 (UP)" or "SW2 (DOWN)". 
Press "SW7" to confirm selecting the mode.   
On the master unit, press "SW6" to return to the upper level.   
If  no  button  operations  are  performed  on  the  master  unit  for  five  minutes,  the  function  setting 
automatically quits and the unit restores the current status.   
  Indoor unit refrigerant recovery 
Step 3: Select "01” as in step 2 to enter IDU refrigerant recovery. Digital LEDs and status LEDs of all