Gree GMV6 DC Inverter VRF Units Service Manual
CA On 04 On OC On
Modules not shielded display as follows:
Press the SW4 back button. Modules not shielded display normal working status, and the shielded
module displays as follows:
Module
Display status
Module failure/indoor unit
Display status Module status Display status
NOTES!
① This function is valid only in systems with two or more modules connected in parallel;
② A system can set only one module to emergency mode;
③ The default status is 00.
④ The system cannot run continuously for more than 48 hours in module emergency operation
status. If it exceeds 48 hours, the entire system is stopped, and the indoor unit displays the
"Ad" limit operation code.
4.2.3.14 1b Adaptive Control of Weather Parameters
Setting steps:
Enter the function setting. The master unit displays as follows by default, and other basic modules
display normal working status:
Press the SW1 up button and the SW2 down button to select the corresponding low pressure control
mode.
Description
Function
Display
Current
Display
Current
Display
1b On 00 Blinks OC Blinks
The adaptive control of weather
1b On 01 Blinks OC Blinks
The adaptive control of weather
After selecting the corresponding mode, press the SW3 confirm button. The master module displays
as follows: