GMV DC Inverter VRF
43
3.8.2 Electrical Parameters
Every unit should have corresponding short-circuit and overload protection. And also a main
switch is required to control power supply or disconnection. See Fig. 3.8.1.
Fig. 3.8.1
Please refer to the following table for outdoor unit power cord specifications and circuit breakers.
Model
Combination
method
Power supply
Capacity of
circuit breaker
of each
combination
module (A)
Minimum cross-sectional
area of grounding wire
(mm
2
)
Recommended
wire
(cross-sectional
area) (mm
2
)
GMV-224WM/H-X -
380-
415V 3N~
50/60Hz
25 2.5
2.5×5
GMV-280WM/H-X -
380-
415V 3N~
50/60Hz
25 2.5
2.5×5
GMV-335WM/H-X -
380-41
5V 3N~
50/60Hz
25 4.0
4.0×5
GMV-400WM/H-X -
380-
415V 3N~
50/60Hz
40 6.0
6.0×5
GMV-450WM/H-X -
380-
415V 3N~
50/60Hz
40 6.0
6.0×5
GMV-504WM/H-X -
380-
415V 3N~
50/60Hz
50 10.0
10.0×5
GMV-560WM/H-X -
380-
415V 3N~
50/60Hz
50 10.0
10.0×5
GMV-615WM/H-X -
380-
415V 3N~
50/60Hz
50 10.0
10.0×5
GMV-680WM/H-X 280+400
380-
415V 3N~
50/60Hz
25+40 2.5+6.0
2.5×5+6.0×5
GMV-730WM/H-X 280+450
380-
415V 3N~
50/60Hz
25+40 2.5+6.0
2.5×5+6.0×5
GMV-784WM/H-X 280+504
380-
415V 3N~
50/60Hz
25+50 2.5+10.0
2.5×5+10.0×5
GMV-840WM/H-X 280+560
380-
415V 3N~
50/60Hz
25+50 2.5+10.0
2.5×5+10.0×5
GMV-895WM/H-X 280+615
380-
415V 3N~
50/60Hz
25+50 2.5+10.0
2.5×5+10.0×5
GMV-950WM/H-X 335+615
380-
415V 3N~
50/60Hz
25+50 4.0+10.0
4.0×5+10.0×5
GMV-1015WM/H-X
400+615
380-415V 3N~
50/60Hz
40+50 6.0+10.0
6.0×5+10.0×5