DC Inverter Side Discharge VRF Ⅱ for North America
123
(3) Calculation example
IDU:
Duct type
GMV-ND18PLS/A-T(U)
Duct type
GMV-ND12PLS/A-T(U)
Duct type
GMV-ND09PLS/A-T(U)
Duct type
GMV-ND09PLS/A-T(U)
Liquid pipe:
Total length of each liquid pipe
Φ9.52:A+B+C+a=10+5+5+3=23m(75-1/2 feet)
Φ6.35: D+b+c+d=5+3+2+1=11m(36feet)
NOTICE! Liquid pipe that is within 20m(65-5/8 feet) doesn’t need to be added with
refrigerant.
Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022=
0.404kg(14oz)
5.3.2 Operation procedure for adding refrigerant
(1) Put the charging tank on the weightometer, record the reading and then calculate the data
after charging refrigerant;
(2) Use charging conduct pipe to connect the double-ended manometer with governing valve