DC Inverter Side Discharge VRF for North America
4
Model
GMV-48WL/A-T(U)
GMV-60WL/A-T(U)
(WxDxH)
inch
39_5/16×18×59_5/8
40_5/8×17×62_3/16
Compressor
QXAS-F428zX050A
LNB53FCFMC
Water-proof level
IPX4
IPX4
Suitable climite
T1
T1
Connectio
n pipe
Gas
mm
Φ15.9
Φ19.05
inch
Φ5/8
Φ3/4
Liquid
mm
Φ9.52
Φ9.52
inch
Φ3/8
Φ3/8
Connection
Method
Bell mouth connection
Bell mouth connection
Net weight
Kg
110
124
oz
3880
4375
Note:
Units conform to design standard: ARI 210/240.
Specifications may be changed due to product improvement. Please refer to
nameplates of the units.
Noise data are collected from a semi-anechoic room. Decibels may be slightly higher
in actual operation due to environmental change.
Refrigerant charge volume listed in the table is based on the condition where indoor
and outdoor units are at a same level and with no connection pipe. Supplementary
refrigerant needs to be charged according to actual circumstance.
3.2 Operation range
Cooling
Outdoor temperature: -5~48 (23~11F)
Heating
Outdoor temperature: -20℃~27(-4~81°F)
4 Product Capacity Correction
4.1 Instruction of Product Capacity Correction
Nominal cooling capacity and nominal heating capacity are tested under given
conditions:
1
Rated cooling or heating condition
2
No height difference between indoor unit and outdoor unit
3
Short connection pipe
If the three conditions above have changed, the cooling and heating capacity will
change correspondingly and correction is needed.
4.2 Capacity Code
Instruction of capacity code
GMV-36WL/A-T(U)
GMV-48WL/A-T(U) and GMV-60WL/A-T(U) are identical in