DC Inverter Side Discharge VRF for North America
5
components, systems and structure, etc. While the required capacity is set through the
capacity DIP switch.
Sheet of DIP Switch (5-bit DIP switch)
Model
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
GMV-36WL/A-T(U)
0
0
1
0
0
GMV-48WL/A-T(U)
0
0
1
0
1
GMV-60WL/A-T(U)
0
1
0
0
0
4.3Capacity Correction Formula
4.3.1Rated capacity of outdoor unit
Model
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
GMV-60WL/A-T(U)
Rated cooling
capacity
kW
11
14.1
17.6
Btu/h
37500
48000
60000
Rated heating
capacity
kW
12.3
15.8
18.7
Btu/h
42000
54000
64000
4.3.2 Correction factor of indoor and outdoor temperature
1
Correction factor of cooling capacity
2
Correction factor of heating capacity