DC Inverter Side Discharge VRF for North America
84
There are two wiring diagrams for communication wires of indoor/outdoor units and
remote monitor:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
There are two wiring diagrams for power cord:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
7.2 Power Cable Wire Gauge and Circuit Breaker Selection
Model
Power supply
Max Fuse
Size/Fusible Max.
(A)
Max Ckt, Bkr
Size/Disjoncteur Max. (A)
Min. Circuit
Ampacity
(A)
GMV-36WL/A-T(U)
208/230V~
60Hz
50
50
32
GMV-48WL/A-T(U)
208/230V~
60Hz
60
60
37
GMV-60WL/A-T(U)
208/230V~
60Hz
70
70
42