DC Inverter Side Discharge VRF Ⅱ for North America
91
Compressor’
s operating
freq
Compressor’
s operating
current
When compressor works normally, the current is no
more than22.6A.
When ambient temp is below 35℃(95℉), IPM temp
is lower than 80℃(176℉) and the highest temp won’t
be above 95℃(203℉).
Fan motor’s
operating
freq
Changes in
0~49Hz
according to
system’s
pressure.
Changes in
0~40Hz
according to
system’s
pressure.
Indoor heat
exchanger’s
inlet temp
According to ambient temp, for a same IDU in cool
mode, the inlet temp will be 1℃~7℃(34~45℉) lower
than the outlet temp, and 4~9℃(39~48℉) higher
than the low pressure value.
For a same IDU in heat mode, the inlet temp will be
10℃~20℃(50~68℉) lower than the outlet temp.
Opening
angle of
indoor EXV
In cool mode, the
opening angle of
indoor EXV
varies within
70~480PLS.
In heat mode,
the opening
angle of indoor
EXV varies
within
70~480PLS.
In cool mode, the
opening angle of
indoor EXV
varies within
70~480PLS.
In heat mode,
the opening
angle of indoor
EXV varies
within
40~480PLS.
Number of IDUs detected by software is the same
with the actual number. No communication error.
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward slope of
water; Water of outdoor unit can be drained
completely through drainage pipe. No water drop
from unit base.
Compressor and indoor/outdoor fan motor do not
have strange noise. Unit can operate normally.