Ultra Heat GMV5 User Manual
8
ODU
IDU
a
Equivalent length to the farthest
connection pipe(L≤150m/492ft)
Equivalent length from the 1st branch
to the farthest pipe(L<4om/131ft)
Height difference
between IDUs(h≤15m/49ft)
L1
IDU
The 1st
branch
section
Height difference between IDU and ODU(H≤50m/164ft)
Each Y-type branch equals to 0.5m(1-5/8ft) and each branch header equals to 1.0m(3-1/4ft).
IDU IDU
L2
L3
b
c
d
Fig.5 Allowable Length and Height Difference of Connection Pipe
Piping parameters of GMV-36WL/B-T(U)
、
GMV-48WL/B-T(U):
Total length (actual length) of fitting pipe
Length of farthest fitting pipe
From the 1
st
branch to the farthest indoor pipe
Height difference between ODU
and IDU
Height difference between IDUs
4.2.3 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch
Dimension of pipe from ODU to the 1
st
indoor branch will be determined by the dimension of
outdoor connection pipe.