Ultra Heat GMV5 User Manual
9
Fig. 6
Dimension of outdoor connection pipe:
Basic module
Pipe dimension
Gas pipe
(mm/inch)
Liquid pipe
(mm/inch)
GMV-36WL/B-T(U)
φ15.9
(φ5/8)
φ9.52
(φ3/8)
GMV-48WL/B-T(U)
φ15.9
(φ5/8)
φ9.52
(φ3/8)
4.2.4 Selection of Indoor Branches
Select indoor branches according to the total capacity of downstream indoor units. if the
capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Fig.7
Refrigerant system
Total capacity of downstream indoor units C (Btu/h)
Model
Y type branch
C< 68200
FQ01A
68200C102400
FQ01B
102400C 238800
FQ02
238800C 460600
FQ03