Ultra Heat GMV5 User Manual
10
460600C
FQ04
4.2.5 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor units; if
the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Fig.8
Total capacity of downstream indoor units
C (Btu/h)
Pipe
(mm/inch)
Liquid pipe
(mm/inch)
C ≤19000
Φ12.7
(Φ1/2)
Φ6.35
(Φ1/4)
19000<C≤48500
Φ15.9
(Φ5/8)
Φ9.52
(Φ3/8)
48500<C≤76400
Φ19.05
(Φ3/4)
Φ9.52
(Φ3/8)
4.2.6 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the dimension of
indoor pipe.