EasyManua.ls Logo

Gree GMV-400WM/B-X - Page 134

Gree GMV-400WM/B-X
375 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
131
Figure 1
2) Solution of project number conflict:
1. Manual setting on the commissioning software:
Use the commissioning software to set IDUs' project numbers separately in every system or
reset projects numbers in multiple systems.
Choose Setting -> Parameter Settings, as shown in Figure 2:
Figure 2
If project commissioning is finished and the IDU where the conflict occurs needs to be set
separately. Click Project Number Conflict, as shown in Figure 3. The pop-up box comprises two
parts: conflicting IDU box, showing the IDU's project number, system number and time; setting

Table of Contents

Other manuals for Gree GMV-400WM/B-X

Related product manuals