GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
179
Current curve
C
onde
ns
i
ng
t
e
m
p
.
Evaporating temp. (°C)
Secondary current (A)
Note: You can infer from the preceding figures the current of the compressor operating at other
frequency bands.
Step 2:
Check whether the compressor sounds sharp or rubs. Compare the sound of the faulty compressor with
that of normal ones.
Step 3:
Check whether the electric expansion valves of ODUs and the 4-way valves act, and whether the oil
return pipes and oil balance valves 1 and 2 are normal. Touch the pipelines next to the return capillary
tubes to check whether there is oil flowing.
Check method for each part:
Electric expansion valve: This valve will reset for each power-on or power-off action. Touch the valve
and you will feel its vibration during the reset action. A crack sound will be heard as well.
Description of electric expansion valve:
Electric expansion
valve of heater
Electric
expansion valve
of subcooler