GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 
86 
Maximum Refrigerant Recovery Volume (kg) 
GMV-400WM/B-X 
GMV-450WM/B-X 
This  function  falls  into  two  modes:  faulty  module  refrigerant  recovery  and  IDU  pipeline  refrigerant 
recovery. 
Refrigerant Recovery 
Mode Code 
Refrigerant Recovery 
Mode Name 
Basic module refrigerant 
recovery 
This mode is selected when a basic module fails and it is required 
to recover refrigerants from this basic module. 
Indoor unit pipeline 
refrigerant recovery 
This mode is selected when an IDU fails and it is required to 
recover refrigerants from the IDU pipeline. 
When this function is enabled, the ODU automatically starts and recovers refrigerants to the ODU or IDU 
pipeline. 
(2) A6 Unit cooling/heating function 
This function sets operation modes of the entire unit, including: 
Cooling mode, dehumidifying mode, heating mode, and air 
supply mode. 
(Note: The heating mode cannot work with other modes at the 
same time.) (factory settings) 
Cooling mode, dehumidifying mode, and air supply mode. 
Heating mode and air supply mode. 
(Note: The heating mode cannot work with the air supply 
mode at the same time.) 
The user or administrator can set operation modes of the ODU based on actual situations to prevent 
conflicts.   
When it is required to set different refrigerating systems to the same function mode, set the master 
system  according  to  the  above  requirements.  For  the  master  system  settings,  see  the "Centralized 
Control Address DIP Switch (SA2_Addr-CC)" section. 
(3) A7 Outdoor silent mode 
This function is used when users require lower environment noises, including nighttime automatic silent 
mode and forcible silent mode.   
For  the  nighttime  automatic  silent  mode,  the  system  automatically  judges  the  highest  daytime 
environment temperature and then starts silent operations in a certain interval to guarantee nighttime 
low-noise operations. The nighttime automatic silent mode falls into nine categories: 
Starting the Silent Mode X Hours 
after the Daytime Temperature 
Reaches the Highest 
Stopping the Nighttime Silent 
Mode after Continual 
Operations for Y Hours 
Low- and 
medium-noise mode