GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 
116 
The system detects pipe 
failure of IDU. "XXXX" 
indicates the project 
number of the faulty IDU. 
The fault code "U8" is 
displayed after three 
seconds. For example, if a 
U8 fault occurs on IDU 
100, LED3 will circularly 
display "01", "00" (two 
seconds later), and "U8" 
(two seconds later). 
Step  18:  If  no  exception  occurs  when  the  unit  continuously  operates  for  40  minutes,  the  system 
automatically confirms commissioning completion, stops the entire unit, and restores the standby status. 
The main board is displayed as follows: 
17_Commissioning 
completion status 
The unit has completed 
commissioning and in 
standby status. LED1 
displays the module 
address; LED2 and LED3 
display "OF".