GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
134
When the project number conflict occurs, you can use the communicator or remote controller to
revise project numbers and solve the conflict. See the manual of the communicator or remote
controller for the method.
Setting of auto project number deviation on ODU's main board (recommended)
You can set auto IDU project number deviation via the ODU's main board as follows:
(1) After the whole system is commissioned, short press SW3 on the controlling unit and the
system will enter the standby status as follows:
LED1
LED2
LED3
Function Code
LED Status
Progress
LED Status
Status
LED Status
A7
Flicker
00
Flicker
00
Flicker
A6
Flicker
00
Flicker
00
Flicker
A2
Flicker
00
Flicker
00
Flicker
A8
Flicker
00
Flicker
00
Flicker
n0
Flicker
01
Flicker
00
Flicker
n1
Flicker
00
Flicker
00
Flicker
n2
Flicker
00
Flicker
00
Flicker
n3
Flicker
00
Flicker
00
Flicker
n4
Flicker
00
Flicker
00
Flicker
n5
Flicker
00
Flicker
00
Flicker
(2) Press SW2 (▼) on the controlling unit and select n5. Short press SW7 to show the
following information:
(3)
When project number deviation is to be confirmed, short press SW7 confirmation button
to enter the project number deviation status as shown in the following:
LED1
LED2
LED3
Function
Code
LED
Status
Current
Progress/Mode
LED
Status
Status
LED Status
n5
Solid On
00
Solid On
OC
Solid On
IDU project numbers in all systems will automatically deviate. The conflict will be solved in about
1 minute and the system will work properly.
The automatic deviation function only works when it is enabled on the controlling unit in the
system, of which the centralized control address is 00000.
Note: When there are only a few conflicting IDUs, manual setting is recommended. This method
only applies to conflicting IDUs and does only affect other IDUs' project numbers.
In case of many conflicting IDUs, auto deviation is recommended. This method is faster, but may
change project numbers of normal IDUs. This method applies for the first commissioning after
installation.
Fault
code
Fault
Possible reasons
Solution
LED1
LED2
LED3
Function Code
LED Status
Progress
LED Status
Status
LED Status
n5
Solid On
00
Flicker
OC
Flicker

Table of Contents

Other manuals for Gree GMV-615WM/B-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-615WM/B-X and is the answer not in the manual?

Gree GMV-615WM/B-X Specifications

General IconGeneral
BrandGree
ModelGMV-615WM/B-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals