GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
36
3. Monsoons must be considered during ODU installation.
Monsoon direction
Incorrect
The defrosting time is prolonged in this case
One side (rear side) of
Fresh-air suction inlet
Monsoon direction
Return air(rear side)
Return air(rear side)
Protective cover
Return air(rear side)
Correct
4. Snow must be considered during ODU installation.
Incorrect
Monsoon
Protective shield of air supply
inlet (provided on site)
Protective shield of air
supply inlet (provided on site)
The possible height of snow must be
considered when determining the height of base
Correct
Monsoon