GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 
77 
m=(m1-m2)+(m3-m4)+…+(mn-1-mn) 
Quantity of refrigerant to be perfused during running m`=M-m 
M is the required total quantity 
If the pre-perfusion quantity (m) reaches the required total quantity for the system, turn off the valve of 
the refrigerant tank immediately to finish perfusing and proceed with step 11. 
Step 11: Remove the pressure gauge. 
 
2. Refrigerant Perfusion During Running 
Step 1: Turn off the valve of the refrigerant tank and reconnect the pressure gauge pipe. Disconnect the 
low pressure gauge pipe from the detection valve opening of the gas liquid and connect it to the 
low pressure detection valve, as shown in the following figure. 
 
Step 2: Turn on the valves for the liquid and gas pipes of each module completely. For the modular unit, 
the oil-equalizing valve of each module also needs to be turned on. 
Step 3: Make the system to run in commissioning mode via the commissioning software or the main 
board of the ODU. (For details, see the description on commissioning.) 
Step 4: When the commissioning step goes to refrigerant perfusion, turn on the valve of the refrigerant 
tank and perfuse the remaining quantity (m`). 
Step 5: After all refrigerant is perfused, turn off valve of the refrigerant tank and wait till commissioning is 
automatically is completed for the system. 
Step 6: Remove the pressure gauge to finish refrigerant perfusion.