EasyManua.ls Logo

Gree GMV-615WM/G-X - Page 146

Gree GMV-615WM/G-X
305 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Gree GMV6 DC Inverter VRF Units Service Manual
144
2.94 "J3" Compressor 3 Over-current Protection
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When the operating current of the compressor detected by the current sensor or circuit exceeds the
limit, the unit will stop working.
Possible causes:
The unit's parameters are abnormal;
The drive module is abnormal;
The compressor is abnormal.
Troubleshooting:
"J3" Compressor 3
Over-current Protection
The compressor is
abnormal
Yes
Yes
Replace the compressor
No
Replace the drive modu le
If the h igh pressu re valu e o f th e u nit
is still above 60°C when the compre ssor runs at the lowest
frequen cy, the compressor may ha ve enabled normal over-current
protection. In this case, check whether th e fan operates properly and
whether the ambient temperature is normal and wheth er the
power supply is normal (320V-460V)
Power on aga in
the units based on the capa city
and nu mber o f indoor u nits enabled
previou sly in the case of
protection state
Whether the drive modu le is normal?
Yes
Yes
Is th e p rotection still occurring
after power-on?
Yes

Other manuals for Gree GMV-615WM/G-X

Related product manuals