GREE DC Inverter Multi VRF System II Service Manual
132
Removal operation of compressor
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the power
is disconnected.
Process Photo
Operation
Instruction
6. Connect
suction pipe and
discharge pipe of
copressor and
pipeline of
system again
Weld the
connection pipe of
compressor,
connect the pipeline
and compressor
Note: During
welding process, do
not let flame burn
out other parts
7. Connect the
power cord of
compressor well
● Loose screws
fixing the power
cord with
screwdriver
● conenct the
power cord well
again
Note: When
connecting the
power cord, make
marks for different
color power cords
and corresponding
wiring terminals.