Gree                GMV6 DC Inverter VRF Units Service Manual 
 
Checklist Before GMV6 Commissioning 
Category  No.  Item  Reference Value  Qualified  Inspector 
Communication 
system 
30 
Does the communication cable 
material meet the unit design 
— 
   
31 
Is the communication connection 
between outdoor unit modules 
— 
   
32 
Is the DIP switch of the master unit 
of the outdoor unit module correct? 
— 
   
33 
Is the communication between the 
outdoor master unit and the indoor 
Serial connection     
34 
Is the communication connection 
between indoor units correct? 
— 
   
35 
Is the communication connection 
between the indoor unit and the 
wired controller correct? 
— 
   
36 
Is the last communication indoor 
unit installed with a communication 
— 
   
37 
The communication cable cannot 
be laid in the same trough as the 
power cable. It is laid separately in 
a flame-retardant hard PVC pipe. 
The parallel spacing between a 
communication cable and a strong-
current cable is greater than 20 cm. 
— 
   
Indoor unit 
installation 
38 
Does the indoor unit drain pipe 
have a slope of 1/100? 
— 
   
39 
Does the height of the indoor unit 
riser drain pipe meet the 
— 
   
40 
Does the indoor unit drain 
smoothly? 
— 
   
41 
Is there a U-shaped trap for indoor 
unit drainage? 
— 
   
42 
Is there a soft joint at the air outlet 
and air return vent of the indoor 
unit? Does the return air have a 
— 
   
43 
Does the indoor unit water pipe 
have an emptying port? 
— 
   
44 
Is a "main" label attached to the 
wired controller or panel of the 
— 
   
 
3.2 Debugging and Operation   
3.2.1 Precautions 
(1)  Do set one (only one) module as the main module during debugging. 
(2)  When there is no special requirement, the other functions do not need to be set, and it can be 
operated according to the factory settings. For special functions, please refer to the related 
technical documents. 
(3)  Installation and debugging operation must comply with the relevant regulations of the local country 
or region.