EasyManua.ls Logo

Gree GMV-PD140W/NAB-K - User Manual

Gree GMV-PD140W/NAB-K
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation and Operation Manual
Instruction of the GMV D.C. Inverter
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Please read this manual carefully before using this product and keep it properly for future reference.
Applicable Models
:
GMV-Pd100W/NaB-K GMVL-Pd100W/NaB-K
GMV-Pd120W/NaB-K GMVL-Pd120W/
NaB-K
GMV-Pd140W/NaB-K GMVL-Pd140W/NaB-K
GMV-Pd160W/NaB-K GMVL-Pd160W/NaB-K

Other manuals for Gree GMV-PD140W/NAB-K

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-PD140W/NAB-K and is the answer not in the manual?

Summary

Safety Considerations

General Safety Guidelines

Read manual carefully, follow instructions, and note warning symbols for safe operation.

Installation Cautions

Check power supply, connections, grounding, and avoid improper operations like stopping unit too soon.

Installation Location: Air Conditioner Unit

Installation Location: Indoor Unit

Installation Location: Outdoor Unit

Location Selection

Firm support, close to indoor unit, avoid noise entry, ensure ventilation, avoid dust/fog/pollution.

Cable and Grounding Requirements

Grounding Requirements

Unit is Class 1 electrical appliance; use dedicated grounding wire, do not connect to pipes.

Outdoor Unit Installation

Installation Precautions

Ensure proper airflow, avoid recirculation, secure mounting, protect during lift, avoid corrosion/snow.

Electrical Cable Connection

Indoor & Outdoor Unit Pipe Connection

DIP Switch Settings

Indoor Unit Address & Capacity Setup

Details setting indoor unit address and capacity using DIP switches on main board and wired controller.

Refrigerant and Test Run

Filling of Refrigerant

Steps for filling refrigerant, including checking valves, vacuuming, and charging R410A.

Calculating Additional Refrigerant

Explains how to calculate additional refrigerant needed based on pipe length and diameter.

Installation Inspection

Checks and Problem Identification

Lists inspection points and potential problems from improper installation.

Test-running Procedures

Steps for Running Test

Procedures for professional test running, including powering units and checking for abnormal noise.

Maintenance Measures

Safety Warnings

Stop unit and shut off power before cleaning; avoid electric shock and damage.

Troubleshooting

Error Codes and Indicators

Lists error codes on wired controller and indicator lights on outdoor unit for troubleshooting.

Overview

This document is an Installation and Operation Manual for a GREE GMV D.C. Inverter air conditioning unit, specifically covering models GMV-Pd100W/NaB-K, GMVL-Pd100W/NaB-K, GMV-Pd120W/NaB-K, GMVL-Pd120W/NaB-K, GMV-Pd140W/NaB-K, GMVL-Pd140W/NaB-K, GMV-Pd160W/NaB-K, and GMVL-Pd160W/NaB-K.

The device is a multi-split air conditioning system designed for both cooling and heating (Heat Pump Type) or cooling only (Cooling Only Type), utilizing a D.C. Inverter compressor for efficient operation. It is capable of connecting one outdoor unit to up to 16 indoor units, offering flexibility in system integration. The indoor units can be of various types, including cassette, wall-mounted, ducted, low hydrostatic pressure ultra-thin, and floor standing types, allowing for diverse installation scenarios and aesthetic preferences.

Function Description:

The GMV D.C. Inverter system provides climate control for indoor spaces. In cooling operation, low-temperature, low-pressure refrigerant gas from the indoor unit heat exchangers is absorbed and compressed by the outdoor unit's compressor into high-temperature, high-pressure gas. This gas then discharges into the outdoor unit's heat exchanger, where it exchanges heat with the outdoor air and transforms into refrigerant liquid. The liquid flows through a Y-type manifold to all indoor units, passes a throttling component to decrease pressure and temperature, and then enters the indoor unit heat exchangers to absorb heat from the room air, changing back into low-temperature, low-pressure gas. This cycle continuously repeats to achieve cooling. For heating operation (heat pump models), a 4-way reversing valve alters the refrigerant flow, causing the indoor unit heat exchanger to radiate heat into the room (with auxiliary electric heating if present) and absorb heat from the outdoor unit's heat exchanger, thereby providing warmth. The system ensures that when any indoor unit receives an operation order, the outdoor unit starts, and when all indoor units stop, the outdoor unit also stops.

Important Technical Specifications:

The manual provides specific technical data for the listed models:

  • Cooling Capacity (kW): Ranges from 10 kW (GMV(L)-Pd100W/NaB-K) to 16 kW (GMV(L)-Pd160W/NaB-K).
  • Heating Capacity (kW): Ranges from 11 kW (GMV(L)-Pd100W/NaB-K) to 17.6 kW (GMV(L)-Pd160W/NaB-K) for heat pump models. Cooling-only units (GMVL Type) do not have a rated heating capacity.
  • Noise (dB(A)): 58 dB(A) for 100W, 120W, 140W models, and 60 dB(A) for 160W models.
  • Compressor Type: Inverter*1 for all listed models.
  • Refrigerant: R410A, with a filling amount of 7.5 kg for all models. Additional refrigerant may be required based on pipe length.
  • Power Supply: 220-240V ~ 50Hz.
  • Power Input (kW):
    • Cooling: 2.86 kW (100W) to 4.98 kW (160W).
    • Heating: 2.6 kW (100W) to 4.85 kW (160W).
  • Rated Current (A):
    • Cooling: 14.2 A (100W) to 23.2 A (160W).
    • Heating: 13.2 A (100W) to 21.9 A (160W).
  • Dimensions (mm) (Width×Depth×Height): 950×340×1250 mm for all models.
  • Water Proof Level: IP24.
  • Weather Type: T1.
  • Pipe Connections:
    • Gas Pipe (mm): φ15.9 for 100W, 120W, 140W models; φ19.05 for 160W models.
    • Liquid Pipe (mm): φ9.52 for all models.
    • Connection Method: Flare Connection.
  • Rated Working Conditions:
    • Cooling: Indoor 27°C DB / 19°C WB; Outdoor 35°C DB / 24°C WB.
    • Heating: Indoor 20°C DB / 15°C WB; Outdoor 7°C DB / 6°C WB.
  • Operating Temperature Range:
    • Cooling: Outdoor 10°C ~ 48°C.
    • Heating: Outdoor -20°C ~ 27°C.
  • Maximum Indoor Units: One outdoor unit can drive up to 16 indoor units.
  • Indoor Unit Capacity Code Sum: The sum of indoor unit capacity codes can be 50%-135% of the outdoor unit capacity code number.
  • Allowable Pipe Lengths:
    • Total length (actual): 150m.
    • Length of farthest fitting pipe (actual): 70m.
    • Length of farthest fitting pipe (equivalent): 80m.
    • Equivalent length from 1st manifold to farthest fitting pipe: 25m.
  • Allowable Drop Heights:
    • Between outdoor and indoor unit (outdoor unit upper): 30m.
    • Between outdoor and indoor unit (outdoor unit lower): 25m.
    • Between indoor units: 10m.

Usage Features:

  • Smooth Start: The main power switch should be turned "ON" 8 hours before the initial start-up for smooth operation.
  • Fan Operation after Stop: After receiving a STOP signal, the indoor unit fan continues to operate for 20-70 seconds to utilize residual cold/hot air and prepare for the next use.
  • Mode Conflict Detection: If an indoor unit's run mode conflicts with the outdoor unit's, a fault indicator will blink, and the indoor unit will stop. Users must switch the indoor unit's mode to resolve the conflict. Cooling mode does not conflict with dehumidify mode, nor fan mode with other modes.
  • DIP Switch Configuration: Indoor units and wired controllers use DIP switches (4-bit or 8-bit) to set address and capacity codes. The wired controller's address must match its corresponding indoor unit.
  • Refrigerant Filling: The outdoor unit is pre-filled with R410A. Additional refrigerant is calculated based on the liquid pipe length and diameter. No additional refrigerant is needed if the total liquid pipe length is within 50m.
  • Test Run Procedure: After installation, a professional test run is required. This involves powering on units, turning on controllers, and observing automatic start-up of indoor fans and compressors. Immediate shutdown is necessary if abnormal noise occurs.

Maintenance Features:

  • Pre-Operational Season Inspection (Beginning of Operational Season):
    • Check for blockages at air inlets/outlets of both indoor and outdoor units.
    • Verify reliable grounding.
    • Check and replace remote controller batteries if needed.
    • Inspect outdoor unit installation for stability.
    • Ensure the main power switch is "ON" 8 hours before starting after a long shutoff.
  • Post-Operational Season Maintenance (End of Operational Season):
    • Clean the filter and housing of the outdoor unit.
    • Shut off the main power supply.
    • Remove dust and foreign articles from the outdoor unit.
  • General Cleaning: Before cleaning, the unit must be stopped, and the main power supply shut off. Do not wet the unit or use hot water above 45°C, volatile liquids (thinner, gasoline). Use a soft dry cloth or a cloth wetted with neutral cleanser.
  • Troubleshooting: The manual includes a comprehensive troubleshooting guide with error codes (E1-Fd) displayed on wired controllers and LED indicators on outdoor unit mainboards. These codes correspond to various issues such as high/low pressure protection, temperature sensor errors, communication errors, and compressor malfunctions, guiding professionals in diagnosis.

Gree GMV-PD140W/NAB-K Specifications

General IconGeneral
BrandGree
ModelGMV-PD140W/NAB-K
CategoryInverter
LanguageEnglish

Related product manuals