Instruction of the GMV D.C. Inverter
9
4.4 Dimension of Connecting Pipe
4.4.1 The tting pipe (main pipe) from outdoor unit to the 1st manifold has the same dimension as
the tting pipe on outdoor unit.
Dimension of Indoor Unit Fitting Pipe
Model
Item
GMV(L)-
Pd100W/NaB-K
GMV(L)-
Pd120W/NaB-K
GMV(L)-
Pd140W/NaB-K
GMV(L)-
Pd160W/NaB-K
Connection
Pipe
Liquid
Pipe
mm φ9.52 φ9.52 φ9.52 φ9.52
Air Pipe mm φ15.9 φ15.9 φ15.9 φ19.05
Connection type belled mouth
Note: If the equivalent length of total t pipe exceeds 90m, the tting pipe on gas side and liquid side shall
be increased of one dimension.
4.4.2 Dimension of the tting pipes (manifold pipe) between manifolds is selected according to
the capacity of the connected downstream indoor unit. The capacity of outdoor unit shall prevail if
exceeded.
Total Capacity of Indoor Units Gas Pipe Liquid Pipe
C≤50 Φ12.7 Φ6.35
50<C≤140 Φ15.9 Φ9.52
140<C≤180 Φ19.05 Φ9.52
4.4.3 The tting pipe (indoor tting pipe) from manifold to indoor unit has the same dimension
as the indoor unit tting pipe. (If the distance from the 1st manifold to an indoor unit exceeds
30m, the tting pipe on gas side and liquid side from the 1st manifold to this indoor unit shall be
increased of one dimension).
Dimension of Indoor Unit Fitting Pipe Unit:mm
Capacity of Indoor Unit Gas Pipe Liquid Pipe
Model 22,25,28 φ9.52 φ6.35
Model32 ,36,40,45,50 φ12.7 φ6.35
Model 36,45,50 φ12.7 φ9.52
Model 56,63,71,80,90,112,125,140 φ15.9 φ9.52
Note: When the capacity of indoor unit less than 5KW, if the distance from the nearest manifold to the
indoor unit exceeds 10m, the tting pipe on liquid side of the pipe shall be increased of one dimension.