Gree                GMV6 DC Inverter VRF Units Service Manual 
 
Note: 
After refrigerant recycle, the system cannot be restarted within 10 minutes. 
Basic module refrigerant recycle: 
Step 3:
 Set the basic module that needs refrigerant recycle to emergency status, close the liquid 
pipe stop valve of the module in emergency status, and then select 02 in step 2 to enter refrigerant recycle 
of the basic module, as shown below: 
LED1  LED2  LED3 
Function code  Display status  Current process  Display status  Current status  Display status 
A2  On  02  On 
On 
LED3 displays the high pressure value of the module. 
Step 4: 
When the high pressure value displayed by LED3 continuously blinks (if the high pressure 
is below 0, 0 is displayed), quickly close the air pipe stop valve of the emergency module, and press SW3 
on the master unit to confirm refrigerant recycle. The entire system will stop immediately. If the high 
pressure value displayed by LED3 continuously blinks and you do not operate in 3 minutes, the system 
forcibly stops. 
Press the SW4 back button on the master module to return to the previous process or exit the function 
setting status. 
Note: 
Before the refrigerant recycle of a basic module, the liquid pipe stop valve of the basic module must 
be closed. After refrigerant recycle, the system cannot be restarted within 10 minutes. 
4.2.3.2 "A6" Cooling/Heating of the Entire System 
Introduction: 
This function sets the cooling/heating mode of the entire system. Available modes include: 
Outdoor Unit Function Mode 
Available Indoor Unit Operation Modes 
Code  Name 
nA 
Cooling and 
heating 
Cooling, dry, heating, and fan 
(Note: Heating mode cannot run with other modes at the same time.) (Default setting) 
nC  Cooling only  Cooling, dry, and fan 
nH  Heating only 
Heating and fan 
(Note: Heating mode cannot run with other modes at the same time.) 
nF  Fan  Fan 
The user or administrator needs to set the mode of the outdoor unit based on the actual usage to 
avoid conflicts. 
Setting steps: 
Step 1:
 Enter A6 cooling/heating setting of the entire system, and ensure that the master module 
displays as follows: 
Step 2:
  Press the SW1 up button and the SW2 down button to select the corresponding 
cooling/heating mode.