MULTI VRF-Ⅱ  INDOOR UNIT SERVICE MANUAL    EUROPEAN/LATIN AMETICA (R410A) 
52 
environment 
temperature 
query 
environment temperature sensor of the master ODU. 
Indoor relative 
humidity query 
In “C17” status, press the “MODE” button to enter the 
indoor relative humidity query interface. Press “▲” or 
“▼” to switch the IDU SN. 
Display mode: 
Temperature area: displays the relative humidity value. 
Timer area: displays the project number of IDU (project 
numberes are arranged from small to large). 
If the HBS network consists of only one IDU, the timer 
area directly displays the IDU relative humidity value in 
the “C17” interface. 
Indoor unit 
project number 
query in the 
communication 
network 
In “C18” status, press the “MODE” button to enter the 
IDU project number query interface. Press “▲” or “▼” to 
switch the IDU SN. 
Cancellation method: 
 If users quit the "C18" query interface within 20 
seconds, the project number display is cancelled. 
 If the query interface is quit after 20 seconds upon 
timeout, press the “ON/OFF” button in power-on or 
power-off status to cancel the project number display. 
 The method for cancelling the project number display 
on any wired controller in the network is the same as . 
 
Display mode: 
  Temperature area: displays the SN of the current 
IDU (project numberes are arranged from small to 
large). 
  Timer area: displays the project number of the 
current IDU. 
Each IDU/wired controller in the network displays its 
own project number (the wired controller circularly 
displays project numberes of IDUs every second from 
small to large). 
Fresh-air IDU 
outlet 
temperature 
query 
In “C20” status, press the “MODE” button to enter the 
fresh-air IDU temperature query interface. Press “▲” or 
“▼” to switch the IDU SN. 
Display mode: 
Temperature area: displays the project number of the 
current IDU (1-16, project numberes are arranged from 
small to large). 
Timer area: displays the fresh-air IDU outlet 
temperature. 
If the HBS network consists of only one IDU, the timer 
area directly displays the fresh-air IDU outlet 
temperature in the "C20" interface. 
Note: 
In parameter query status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing the “ON/OFF” 
button, users can return to the main interface but not power on/off the unit.   
In parameter query status, signals of the remote controller are invalid. 
5.1.4 User Parameter Settings 
User parameters can be set in power-on or power-off status. 
(1)  Press and hold the “FUNCTION” button for five seconds. The temperature area displays “C00”. Press