GREE GMV5 INDOOR UNIT SERVICE MANUAL
136
1.2.7 dA IDU network address error
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Through testing the IDU address chip and IP address, if address chip cannot be read, IDU IP is 0 or
IP is in conflict, report the error.
Possible reason:
ODU allocated address is wrong
IDU treatment is wrong
Address chip is abnormal
Troubleshooting:
1.2.8 dH wired controller circuit board error
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Wired controller IIC communication is abnormal
Possible reason:
Communication of wired controller touch button board and display board IIC is abnormal;
Read and write of wired controller memory chip IIC is abnormal (when memory chip is existed);
Troubleshooting: