GREE                                                                                          GMV5 INDOOR UNIT SERVICE MANUAL   
 
76 
 
to enter the wired controller  engineering parameter setting interface.  The temperature area 
displays “P00”. 
(2)  Select  a  parameter  code  by  pressing  “ ”  or  “ ”.  Press  the  “MODE”  button  to  switch  to 
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing 
“ ” or “ ” and then press the “SWING” button to complete settings. 
(3)  Press the “SWING” button to return to the upper-level menu till quitting parameter settings. 
For the engineering parameter setting list of the XK49 wired controller, refer to the engineering setting 
query list in 
XK46 engineering parameter settings
. 
Note:
 In parameter settings, the function of “SWING” on the XK49 wired controller is equivalent to the 
function of “ENTER/CANCEL” on the XK46 wired controller. 
5.3 Engineering Application Functions Operated through the 
XK79 Wired Controller 
 
5.3.1 Master IDU Settings 
The master IDU can be set through the wired controller or remote controller. The methods for setting 
the master IDU through the wired controller are as follows:   
Method 1: 
Step 1: Set an IDU to power-off status. 
Step 2: Press and hold the “MODE” button on the wired controller for more than five seconds. 
Step 3: Check whether the setting is successful. If it is, “MASTER” on the wired controller will be on. 
Otherwise, repeat steps 1 and 2.