MULTI VRF- INDOOR UNIT SERVICE MANUAL EUROPEAN/LATIN AMETICA (R410A)
18
Notes:
Rated cooling capacity test conditions: indoor 27°C DB/1C WB, outdoor 35°C DB; connection
pipe length: 5 m, without height drop between units.
Rated heating capacity test conditions: indoor 20°C DB, outdoor 7°C DB/6 °C WB; connection
pipe length: 5 m, without height drop between units.
3.7 1-way Cassette Type
Model
GMV-
ND22TD/A-
T
GMV-
ND28TD/A-
T
GMV-
ND36TD/A-
T
GMV-
ND45TD/A-
T
GMV-
ND50TD/A-
T
Horse Power
HP
1
1
1.5
2
2
Cooling capacity
kW
2.2
2.8
3.6
4.5
5.0
Heating capacity
kW
2.5
3.2
4.0
5.0
5.6
Air volume
m
3
/h
600
600
600
830
830
Cooling power input
W
30
30
30
45
45
Cooling current input
A
0.2
0.2
0.2
0.3
0.3
Heating power input
W
30
30
30
45
45
Heating current input
A
0.2
0.2
0.2
0.3
0.3
*Minimum line current
A
0.25
0.25
0.25
0.38
0.38
*Maximum fuse current
A
6
6
6
6
6
Sound pressure level
dB(A
)
36
36
36
40
40
Power supply
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Piping interface
Liquid pipe
mm
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Gas pipe
mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ12.7
Drain pipe
External
diameter ×
thickness
mm
Φ25×2.5
Φ25×2.5
Φ25×2.5
Φ25×2.5
Φ25×2.5
Main body
dimensions
H
mm
987×385×17
8
987×385×17
8
987×385×17
8
987×385×17
8
987×385×17
8
Panel
dimensions
H
mm
1200×460×5
5
1200×460×5
5
1200×460×5
5
1200×460×5
5
1200×460×5
5
Net weight
Main body
kg
20
20
20
21
21
Panel
kg
4.2
4.2
4.2
4.2
4.2
Notes:
Rated cooling capacity test conditions: indoor 27°C DB/1C WB, outdoor 35°C DB; connection
pipe length: 5 m, without height drop between units.
Rated heating capacity test conditions: indoor 20°C DB, outdoor 7°C DB/6 °C WB; connection
pipe length: 5 m, without height drop between units.