ERV+DX coil
9
Measuring unit: mm
Model K L N M O P Q R S
GMV-VDR5PH/SA-S 328 226 196 250 175 200 130 247 185
GMV-VDR8PH/SA-S
482 268 230 268 217 207 159 123 53
GMV-VDR10PH/SA-S
NOTE!
Due to individual differences in production assembly, above figures may vary from
those of the present products. Please refer to the actual dimensions of your product.
2.4 Performance Parameters
Table 2-3 Performance parameters
Model
GMV-VDR5PH/
SA-S
GMV-VDR8PH/
SA-S
GMV-VDR10PH/
SA-S
Power supply V 220–240
Rated frequency Hz 50/60
Power input W 270 440 640
Cooling capacity W 8500 12000 14500
Heating capacity W 4000 10600 12000
Fresh air
conditioning
load
Cooling W 3600 6300 8000
Heating W 2000 8040 8400
Fresh air volume
m
3
/h
500 800 1000
External static pressure Pa 150 150 150
Thermal efficiency % 73 74 73
Noise dB 55 59 62
Weight kg 120 158 158
Connection pipe size of duct
type
mm 200 250 250
NOTES!
(1) Airflow volume data is the value tested under the condition of rated static
pressure in high fan speed, subject to actual installation condition, there might
be certain deviation.