EasyManua.ls Logo

Gree GMV-VDR5PH/SA-S - Daily Error Inquiry and Maintenance; Error Diagnosis

Gree GMV-VDR5PH/SA-S
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ERV+DX coil
31
Parameter
setting of
outdoor
pollution level
[default-02]
01Excellent
02Good
03Mild pollution
04Moderate pollution
05Severe pollution
06Serious pollution
It is used to calculate the time
for
cleaning and replacement
reminder.
NOTE!
If need to clean or replace the filter at fresh air side or discharge side of filter, the
wired controller will display the corresponding cleaning replacement hint in text.
(2) Defrosting setting
Fresh air temperature will decrease suddenly due to defrosting when the unit is
conducting heating. If the user requires constant indoor temperature, please reduce
the operating fan speed in project parameter setting when conducting defrosting, to
enhance usage comfort. Users can set the fan status during defrosting through the
wired controller to the lowest fan, current fan or stop the fan:
1) If set wiring controller operate fan speed, the unit air outlet temperature will
be lower, it will influence the comfort.
2) If set lower fan speed, the unit air outlet temperature will be a little higher, it
will enhance usage comfort.
3) If set stop the unit, the unit will stop to operate.
(3) Positive and negative setting
If the user has special requirement on indoor supply air, conduct pertinent setting
in project parameter for different supply air mode.
Positive and
negative
setting
Balanced
(defaulted)
Under this mode, the fan speed setting of fresh air and
discharge is consistent with wired controller
Positive pressure
Under this mode, the fan speed setting of wired controller
is fresh air, the fan speed of fresh air is higher than that of
discharge
Negative pressure
Under this mode, the fan speed setting of wired controller
is discharge, the fan speed of discharge is higher than
that of fresh air
NOTE!
Detailed setting method shall refer to the specification of wired controller.
5 Daily Error Inquiry and Maintenance
5.1 Error Diagnosis
After device debugging and pilot run, the user can use the unit normally. If the

Related product manuals