ERV+DX coil
26
2) When the unit is installed in place, use a level bar to adjust the levelness
of
the unit. Make sure the unit is horizontal from front to back and has an
inclination of 0.5~1° from side to side so that water can be drained
through
the drainage port.
Figure 3-12 Inclination of the unit
NOTES!
(1) Make sure the installation location is strong enough to withstand the weight
of
the unit.
(2) Add a spring rubber damping cushion if necessary.
(3) The selected installation location won’t affect water drainage and pipe
connection.
(4) If the unit is installed in a place where there is oil mist, oil gas or risk of
leakage
of inflammable gas, such as a kitchen, fire hazard may occur.
(5) If the unit is installed in a humid place or near a bathroom, electric leakage or
electric shocks may occur.
(6) If radioactive or electromagnetic equipment is placed near the installation
location, the unit may fail to work.
(7) If the unit is installed in a place with high pH value or large voltage
fluctuation, it
may be damaged.
(8) Power cables of indoor and outdoor units as well as connecting wires should
be
at least 1m away from TV and radios. This is to prevent the electric
appliances
from having image interference and noise. (If interference still
occurs at a
distance of 1m, please increase the distance or ask for
professional help.).