Gree GMV6 DC Inverter VRF Units Service Manual
241
When the compressor frequency is 120 Hz, the current curve corresponding to the evaporation
temperature and condensation temperature is shown as follows:
When the compressor is working at another frequency, the current curve can be obtained through
interpolation calculation of the above frequency.
(2) Inverter compressor DA80PHDG-A1Y2:
When the compressor frequency is 30 Hz, the current curve corresponding to the evaporation
temperature and condensation temperature is shown as follows:
When the compressor frequency is 60 Hz, the current curve corresponding to the evaporation
temperature and condensation temperature is shown as follows: