Step 6: Removing compressors 
Check the damage of compressors, including the number of damaged compressors, positions and 
models. 
After confirming the compressor information, remove the compressors and confirm the oil quality. If 
the oil is clear with no impurity, it can be considered that the oil in the system is not polluted. When the 
valves and oil passages of the unit are normal, only the compressors need to be replaced. 
Vapor injection tube 
welding point of 
compressor 2
Suction pipe welding 
point of compressor 1
Vapor injection tube 
welding point of 
compressor 1
Suction pipe welding 
point of compressor 2
Air discharge pipe 
welding point of 
compressor 2
Remove the fixing bolt of 
compressor 2
Remove the fixing bolt of 
compressor 1
Air discharge pipe 
welding point of 
compressor 1
Compressor 2
Compressor 1
 
The procedure of checking oil quality is described as follows: 
①  After removing a compressor, shake the compressor on a solid ground in the sway angle of 
30 to 45 degrees to ensure that the pollutants deposited on the bottom of the compressor can be 
poured out. 
Remove the compressor 
and shake it on solid 
ground anticlockwise
30-45°