Gree GMV6 DC Inverter VRF Units Service Manual
321
Outdoor units Combination
Power Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
Cross-sectional
Area of Power
615+615
40+40 38.0+38.0 40+40 4*6.0+4*6.0
615+680
40+45 38.0+40.9 40+45 4*6.0+4*10.0
680+680
45+45 40.9+40.9 45+45 4*10.0+4*10.0
20+30+40 21.0+25.0+36.2 20+30+40 4*4.0+4*4.0+4*6.0
20+40+40 20.0+36.2+38.0 20+40+40 4*4.0+4*6.0+4*6.0
20+40+40 20.0+38.0+38.0 20+40+40 4*4.0+4*6.0+4*6.0
20+40+40 21.0+38.0+38.0 20+40+40 4*4.0+4*6.0+4*6.0
30+30+40 25.0+25.0+38.0 30+30+40 4*4.0+4*4.0+4*6.0
30+40+40 25.0+36.2+38.0 30+40+40 4*4.0+4*6.0+4*6.0
30+40+40 25.0+38.0+38.0 30+40+40 4*4.0+4*6.0+4*6.0
40+40+40 36.2+38.0+38.0 40+40+40 4*6.0+4*6.0+4*6.0
40+40+40 38.0+38.0+38.0 40+40+40 4*6.0+4*6.0+4*6.0
40+40+45 38.0+38.0+40.9 40+40+45 4*6.0+4*6.0+4*10.0
40+45+45 38.0+40.9+40.9 40+45+45
45+45+45 40.9+40.9+40.9 45+45+45
20+30+40+40
20+30+40+40
30+30+40+40
30+30+40+40
30+40+40+40
30+40+40+40
30+40+40+40
30+40+40+40
40+40+40+40
40+40+40+40
40+40+40+40
40+40+40+40
30+40+40+45
30+40+40+45
40+40+40+45
40+40+40+45
40+40+40+45
40+40+40+45
40+40+45+45
40+40+45+45
4*6.0+4*6.0+4*10.0
+4*10.0
40+45+45+45
40+45+45+45
4*6.0+4*10.0+4*10.
0+4*10.0
45+45+45+45
45+45+45+45
4*10.0+4*10.0+4*1
0.0+4*10.0
NOTICE!
1. Copper-core cable which complies with local regulations must be applied.
2. According to on-site installation conditions, local regulations must be met.